41
Appendix F (cont'd.)
Object Identifier Object Name Object Type Present Value/Range
Binary Input, 59 AI #9 Failure BINARY_INPUT 1 = Failure 0 = O.K.
Binary Input, 60 AI #10 Failure BINARY_INPUT 1 = Failure 0 = O.K.
Binary Input, 61 AI #11 Failure BINARY_INPUT 1 = Failure 0 = O.K.
Binary Input, 62 AI #12 Failure BINARY_INPUT 1 = Failure 0 = O.K.
Binary Input, 63 AI #13 Failure BINARY_INPUT 1 = Failure 0 = O.K.
Binary Input, 64 AI #14 Failure BINARY_INPUT 1 = Failure 0 = O.K.
Binary Input, 65 AI #15 Failure BINARY_INPUT 1 = Failure 0 = O.K.
Binary Input, 66 AI #16 Failure BINARY_INPUT 1 = Failure 0 = O.K.
Binary Input, 67 Isolation Valve #1 BINARY_INPUT 1 = Open 0 = Closed
Binary Input, 68 Isolation Valve #2 BINARY_INPUT 1 = Open 0 = Closed
Binary Input, 69 Isolation Valve #3 BINARY_INPUT 1 = Open 0 = Closed
Binary Input, 70 Isolation Valve #4 BINARY_INPUT 1 = Open 0 = Closed
Binary Input, 71 Isolation Valve #5 BINARY_INPUT 1 = Open 0 = Closed
Binary Input, 72 Isolation Valve #6 BINARY_INPUT 1 = Open 0 = Closed
Binary Input, 73 Request to Stage Chiller BINARY_INPUT 1 = Yes 0 = No
Binary Input, 74 Request to De-stage Chiller BINARY_INPUT 1 = Yes 0 = No
Binary Input, 75 General Alarm BINARY_INPUT 1 = Alarm 0 = O.K.
Binary Output, 1 Pump Sequence Alternation BINARY_OUTPUT 1 = Yes 0 = No
Binary Output, 2 System Reset Request BINARY_OUTPUT 1 = Yes 0 = No
Binary Output, 3 System Start / Stop BINARY_OUTPUT 1 = Start 0 = Stop
Analog Value, 1 Process Variable #1 ANALOG_VALUE 0 to Span (in Technologic User Setup Menu)
Analog Value, 2 Process Variable #2 ANALOG_VALUE 0 to Span (in Technologic User Setup Menu)
Analog Value, 3 Process Variable #3 ANALOG_VALUE 0 to Span (in Technologic User Setup Menu)
Analog Value, 4 Process Variable #4 ANALOG_VALUE 0 to Span (in Technologic User Setup Menu)
Analog Value, 5 Process Variable #5 ANALOG_VALUE 0 to Span (in Technologic User Setup Menu)
Analog Value, 6 Process Variable #6 ANALOG_VALUE 0 to Span (in Technologic User Setup Menu)
Analog Value, 7 Process Variable #7 ANALOG_VALUE 0 to Span (in Technologic User Setup Menu)
Analog Value, 8 Process Variable #8 ANALOG_VALUE 0 to Span (in Technologic User Setup Menu)
Analog Value, 9 Process Variable #9 ANALOG_VALUE 0 to Span (in Technologic User Setup Menu)
Analog Value, 10 Process Variable #10 ANALOG_VALUE 0 to Span (in Technologic User Setup Menu)
Analog Value, 11 Process Variable #11 ANALOG_VALUE 0 to Span (in Technologic User Setup Menu)
Analog Value, 12 Process Variable #12 ANALOG_VALUE 0 to Span (in Technologic User Setup Menu)
Analog Value, 13 Process Variable #13 ANALOG_VALUE 0 to Span (in Technologic User Setup Menu)
Analog Value, 14 Process Variable #14 ANALOG_VALUE 0 to Span (in Technologic User Setup Menu)
Analog Value, 15 Process Variable #15 ANALOG_VALUE 0 to Span (in Technologic User Setup Menu)
Analog Value, 16 Process Variable #16 ANALOG_VALUE 0 to Span (in Technologic User Setup Menu)
Analog Value, 17 System Flow ANALOG_VALUE 0 to Span (in Technologic User Setup Menu)
Analog Value, 18 Reserved ANALOG_VALUE 0 to Span (in Technologic User Setup Menu)
Analog Value, 19 System KW ANALOG_VALUE 0 to Span (in Technologic User Setup Menu)
Analog Value, 20 KW #1 ANALOG_VALUE 0 to Span (in Technologic User Setup Menu)
Analog Value, 21 KW #2 ANALOG_VALUE 0 to Span (in Technologic User Setup Menu)
Analog Value, 22 KW #3 ANALOG_VALUE 0 to Span (in Technologic User Setup Menu)
Analog Value, 23 KW #4 ANALOG_VALUE 0 to Span (in Technologic User Setup Menu)
Analog Value, 24 KW #5 ANALOG_VALUE 0 to Span (in Technologic User Setup Menu)
Analog Value, 25 KW #6 ANALOG_VALUE 0 to Span (in Technologic User Setup Menu)
Analog Value, 26 Sys Diff Pressure ANALOG_VALUE 0 to Span (in Technologic User Setup Menu)
Analog Value, 27 Sys Supply Temp ANALOG_VALUE 0 to Span (in Technologic User Setup Menu)
Analog Value, 28 Sys Return Temp ANALOG_VALUE 0 to Span (in Technologic User Setup Menu)
Analog Value, 29 Setpoint #1 ANALOG_VALUE 0 to Span (in Technologic User Setup Menu)
Analog Value, 30 Setpoint #2 ANALOG_VALUE 0 to Span (in Technologic User Setup Menu)
Analog Value, 31 Setpoint #3 ANALOG_VALUE 0 to Span (in Technologic User Setup Menu)
Analog Value, 32 Setpoint #4 ANALOG_VALUE 0 to Span (in Technologic User Setup Menu)
Analog Value, 33 Setpoint #5 ANALOG_VALUE 0 to Span (in Technologic User Setup Menu)