INSTALLER: PLEASE LEAVE THIS MANUAL FOR THE OWNER’S USE.SAFETYINSTRUCTIONSThis safety alert symbol will be used in this manual and on theSafety Instru
Xylem Inc. 10661 Newkirk Street Dallas, TX 75220 Phone: (469) 221-1200 Fax: (214) 357-5861www.xyleminc.com/brands/bellgossettBell & Gossett is a t
2SECTION 1 Page 1.0 General Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
31.0 GENERAL DESCRIPTIONThe Glycol Make-up unit is designed to automaticallymaintain minimum pressure in closed-loop systems.The GMU-30 uses 1/2
42.0 INSTALLATION INSTRUCTIONSLocate the Glycol Make-up unit for ease of inspec-tion, maintenance, and service. For Glycol applicationsecondary
53.0 PUTTING THE UNIT INTO SERVICEGMU30 is designed for systems requiring up to 30-psi, drawing water or water-glycol mixture up to10-gpm fr
6SYSTEM PIPING AND UNITINSTALLATION – FINAL CHECK LIST____ 1. Is the unit base properly leveled and secured?____ 2. Are all lubrication points properl
7Appendix C – TroubleshootingPump will not operate:1) Check incoming power2) Check motor overload. Reset if tripped.3) With contactor pulled in, c
8Appendix D – Typical Field Piping - IFC008LOW WATERCUT OFF SWITCHY-STRAINERPUMP2" OPENINGTANK55 GALLONSTRIPLEDUTY VALVEPRESSURE SWITCHPRESSURE G
9Appendix E – Wiring Diagram - 1GMU01