MK, MV (8202, 8202X)Installation,Operation, andMaintenance Manual

Seite 2

Transportation and StorageInspect the deliveryInspect the package1. Inspect the package for damaged or missing items upon delivery.2. Note any damaged

Seite 3 - Table of Contents

Lifting eyeboltsWhen lifting eyebolts are used for lifting the unit, the following guidelines apply:• they always have to be screwed in firmly against

Seite 4

If the unit has been exposed to freezing temperatures, then allow it to reach the ambienttemperature of the sump before operating.Lifting the unit out

Seite 5 - Introduction and Safety

Product DescriptionPump designThe pump is submersible, and driven by an electric motor.Intended useThe product is intended for moving wastewater, slud

Seite 6 - Environmental safety

PositionPart Description1 Shaft Stainless steel with an integrated rotor2 Stator housing Cooled by ambient liquid3 Motor For information about the mot

Seite 7 - User safety

Position Part Description2 ImpellerD-impellerK-impeller3 Mechanical sealsType: Mechanical face seal4Oil housing The oil housing includes a coolant tha

Seite 8 - Ex-approved products

Ex- and MSHA-approved products also have approval plates. They are described below, ifapplicable.21312 1422212017 18 1916159 10 118765431WS000351A1. C

Seite 9 - Product warranty

6. Additional information7. Insulation class8. Max. amperes9. Impeller diameterApprovalsThis section describes the special approvals that explosion-pr

Seite 10 - Transportation and Storage

InstallationInstall the pumpDANGER:Disconnect and lock out electrical power before installing or servicing the unit.WARNING:• Note that special rules

Seite 11

Install with guide railIn the P-installation, the pump is installed on a stationary discharge connection, andoperates either completely or partially s

Seite 13 - Product Description

5. Install the guide bars:a) Secure the guide bars in the bracket.b) Check that the guide bars are placed vertically. Use a level or a plumb line.6. C

Seite 14

3. Lower the pump into the sump.4. Place the pump on the base and make sure it cannot fall over or sink.Alternatively, the pump can be suspended with

Seite 15 - The data plate

• The thermal contacts/thermistors must be in use.• For FM-approved pumps, a leakage sensor must be connected and in use in order tomeet approval requ

Seite 16

6. Connect the mains leads (L1, L2, L3, and earth (ground)) according to applicable cablechart.The earth (ground) conductor must be 50 mm ( 2.0 in.) l

Seite 17 - Approvals

L2L1 L2 L3L3L1WS000509BWS000509CL2L3L1L1L3L2T1T2Figure 4: Phase sequenceConnection locationsThe figures in this section illustrate how to interpret the

Seite 18 - Installation

L1 L2 L3T3 T4T1 T24321586LD97WS004846B1. Starter equipment and mains leads (L1, L2, L3)2. Earth (ground)3. Functional ground4. Control leads (T1, T2,

Seite 19 - Install with guide rail

Colors and marking of leads772 17 05/2Motor connectionColors and marking of main leadsCOLOR STANDARDSTATOR LEADSBN = BrownU1,U5 = RDBK = BlackU2,U6 =

Seite 20 - Install with stand

3-phase connection3 PHASE 6 LeadsYL1U1U2W2V2W1V1L3L2U1V1W1U2W2V2U1V1W1W2U2V2U1V1W1GCW2U2V2L1L2L3*YEGN/YEDL1W2U1W1U2L3V2V1L2U1V1W1W2U2V2U1V1W1W2U2V2U1V

Seite 21

Y-3 PHASE 9 LeadsL3W1U1L1W2U2W5U5V2V1V5L2U1V1W1V2U5V5W5U2W2U1V1W1U1V1W1GCL1L2L3*YEGN/YEY-SERL1U1U2U5W2W5W1V5V2V1L3L2U5U2V5V2W5W2U1V1W1U1U5V1V5W1W5GCL1

Seite 22

Y-3 PHASE 12 LeadsL1U1U5U2W2U6W1V6W6V2V5W5L3V1L2U1V1W1U2V6U5V5W5V2W2U6W6U1V1W1W2U2V2U1V1W1W2GCU2V2L1L2L3*YEGN/YEY-SERL1U1U2U5W6U6W2W5V6W1V5V2V1L3L2U1V

Seite 23 - Cable charts

Table of ContentsIntroduction and Safety...

Seite 24 - Figure 4: Phase sequence

1-phase connection1 PHASE 4 Leads1 ~Z2U2U1Z1T1T2BKBNRDYEGC1/BN*RD2/BK*BK3/GY*WH4/T1*OG5/T2*BU6WHGN/YE*YEStarter1 PHASE 12 Leads1 ~U1V1W1U2V2W2U5V5W5U6

Seite 25 - T3 T4T1 T2

Sensors connectionSENSORS*IF Y/D-start, sensors not connectedControlSUBCAB 4GX/7G SUBCAB AWG H07RN-F*T1WH T1OGBK 4T2WH T2BUBK 5(Thermal Contacts) TCM

Seite 26 - Motor connection

Check the impeller rotationWARNING:The starting jerk can be powerful.1. Start the motor.2. Stop the motor after a few seconds.3. Check that the impell

Seite 27 - 3 PHASE 6 Leads

OperationPrecautionsWARNING:• Never operate the pump without safety devices installed.• Never operate the pump with the discharge valve closed.• Make

Seite 28 - 3 PHASE 9 Leads

WARNING:• Make sure that the unit cannot roll or fall over and injure people or damage property.• In some installations, the pump and the surrounding

Seite 29 - 3 PHASE 12 Leads

MaintenancePrecautionsDANGER:Disconnect and lock out electrical power before installing or servicing the unit.WARNING:• Always follow safety guideline

Seite 30 - 1 PHASE 12 Leads

PropertyclassM4 M5 M6 M8 M10 M12 M16 M20 M24 M30100 4.1 (3) 8.1 (6) 14 (10) 34 (25) 66 (49) 115 (84.8) 248 (183) 481 (355) — —Table 2: Steel, torque N

Seite 31 - (Thermal Contacts)

WS001760A2. Place a container under the pump and turn the pump.3. Unscrew the other oil plug.If this hole has the markings "oil in", raise t

Seite 32 - Check the impeller rotation

WS001762A4. Refit the oil plug and tighten.Tightening torque: 10-40 Nm (7.5-29.5 ft-lbs)Service the pumpType of service Purpose Inspection intervalInit

Seite 33 - Operation

Service item ActionCable1. If the outer jacket is damaged, replace the cable.2. Check that the cables do not have any sharp bends and are notpinched.C

Seite 34

Distance to wet areas...31Noise l

Seite 35 - Maintenance

Service item ActionSupport and main bearing Replace the bearings with new bearings.Mechanical seal Replace with new seal units.Service in case of alar

Seite 36 - Change the oil

a) Remove the pump housing screws.b) Lift off the drive unit from the pump housing.2. Remove the impeller:a) Place the drive unit horizontally.b) Remo

Seite 37

TroubleshootingIntroductionFollow these guidelines when troubleshooting the pump:• Disconnect and lock out the power supply except when conducting che

Seite 38 - Service the pump

Cause Remedy• The impeller• The sump in order to prevent the impeller from clogging again.If the problem persists, contact the local sales and service

Seite 39 - Major overhaul

The pump runs but the motor protection tripsWARNING:Always disconnect and lock out power before servicing to prevent unexpected startup.Failure to do

Seite 40 - Replace the impeller

NOTICE:Do NOT override the motor protection repeatedly if it has tripped. Doing so may result inequipment damage.Cause RemedyThe impeller rotates in t

Seite 41 - Install the impeller: D, K

Technical ReferenceMotor dataFeature DescriptionMotor type Squirrel-cage induction motorFrequency 60 HzSupply 1-phase or 3-phaseStarting method Direct

Seite 43

Xylem |’zīləm|1) The tissue in plants that brings water upward from the roots2) A leading global water technology companyWe're 12,500 people unifi

Seite 44

Introduction and SafetyIntroductionPurpose of this manualThe purpose of this manual is to provide necessary information for:• Installation• Operation•

Seite 45

Hazard levelsHazard level IndicationDANGER: A hazardous situation which, if not avoided, will result indeath or serious injuryWARNING: A hazardous s

Seite 46 - Technical Reference

WARNING:Do NOT send the product to the Xylem manufacturer if it has been contaminated by anynuclear radiation. Inform Xylem so that accurate actions c

Seite 47

Condition ActionChemicals or hazardousfluids in eyes1. Hold your eyelids apart forcibly with your fingers.2. Rinse the eyes with eyewash or running wate

Seite 48 - Xylem

Minimum permitted liquid levelSee the dimensional drawings of the product for the minimum permitted liquid levelaccording to the approval for explosio